Solar Wind Load Calculator (IS 875)
Wind Load Calculator
Design wind pressure and structural load per module as per IS 875 Part 3. Adjust any input and the result updates live.
Inputs
Updates liveIS 875 gives none for solar arrays. Use the racking maker's wind-tunnel value; edge and corner rows see more uplift.
Coastal belt: 60 km wide on the east coast and the Gujarat coast (IS 875-3 clause 6.3.4). Post-cyclone importance: cyclone shelters, hospitals, schools, communication towers.
Results
LiveModerate wind zone
Wind Pressure
N/m²
Uplift / Module
kN
Lateral / Module
kN
Structural Category
Moderate (30–47 m/s)
“IS 875 Part 3 (2015): Vz = Vb·k1·k2·k3·k4 and pz = 0.6·Vz². k1 from Table 1, k2 from Table 2 at the roof height, k4 from clause 6.3.4 (cyclone belt). The standard has no pressure coefficients for solar arrays: the uplift coefficient is an input.”
About the Wind Load (Rooftop)
Wind load is the design pressure the wind exerts on solar modules and their mounting structure. It is the governing load for most rooftop and ground-mount solar in India and sets member sizes, clamp spacing, and foundations — computed per IS 875 Part 3.
Last updated · How we build our calculators
Formula
Vz = Vb × k1 × k2 × k3 × k4 · pz = 0.6 × Vz² (N/m²)
- Vb
- Basic wind speed for the location (m/s), IS 875 Part 3 map: 33 to 55 m/s
- k1
- Risk coefficient (Table 1)
- k2
- Terrain and height factor at the roof height (Table 2)
- k3
- Topography factor
- k4
- Importance factor for the cyclonic region (cl. 6.3.4): 1.15 for industrial structures, 1.30 for structures needed after a cyclone, within 60 km of the east coast and the Gujarat coast
Uplift per module = Cp × pz × module area
- Cp
- Net uplift coefficient — IS 875 has none for solar arrays, so it is an input (default 1.3); use the racking maker's wind-tunnel values for design
How to calculate it
- 1Get the basic wind speed Vb for the site from the IS 875 Part 3 map.
- 2Apply k1 for risk, k2 for terrain at the roof height, k3 for topography, and k4 in the cyclone belt.
- 3Compute the design wind pressure pz = 0.6 × Vz².
- 4Multiply by the net uplift coefficient and the module area for the uplift on each module.
Worked example
Vb = 44 m/s with k1 = k2 = k3 = k4 = 1 (the calculator's defaults): pz = 0.6 × 44² = 1,162 N/m². A 2.583 m² module with Cp 1.3: uplift = 1.3 × 1,162 × 2.583 = 3,901 N.
What you can calculate
- IS 875 Part 3
- Uplift & lateral
- Wind pressure
- 6 wind zones
Standards & references
Frequently asked questions
What wind speed are solar structures designed for in India?
Basic wind speeds in IS 875 Part 3 range from 33 m/s to 55 m/s depending on the region (coastal and cyclone-prone zones are highest). The mounting structure and foundations are designed for the resulting design wind pressure at the site.
Ready to build your solar project?
Get free quotes from verified EPCs and installers across India.
You might also need
Pedestal Height
Calculate front and rear pedestal heights for target module tilt on flat rooftops
OpenModule Layout Planner
Plan tables, rows and string configuration for a rooftop array
OpenSetback from Parapet
Calculate minimum module setback from parapet walls to avoid shading
OpenBallast Weight
Calculate ballast required to resist IS 875 Part 3 wind uplift without penetrations
OpenAnchor Bolt Sizing
Check anchor bolt steel tension (IS 800) against factored wind uplift and count the bolts
OpenStructure Material BOQ
Estimate structural steel, channels, clamps and hardware quantities from module count
Open